Mitsubishi Electric MELSEC Q Series User Manual page 484

Programmabale web server module
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

9 TROUBLE SHOOTING
Error
Error name
code
0612h
File creation error
0613h
File write error
0614h
Directory creation error
Excessive number of
0615h
saved logging files
error
0616h
Send queue error
0617h
Module stop error
9 - 29
Error definition
At start-up or setting update, the
following was detected.
 Failed to create a file.
At other than start-up or setting
update, the following was
detected.
 Failed to create a file.
At start-up or setting update, the
following was detected.
 Failed to write a file.
At other than start-up or setting
update, the following was
detected.
 Failed to write a file.
At start-up or setting update, the
following was detected.
 Failed to create a directory.
At other than start-up or setting
update, the following was
detected.
 Failed to create a directory.
At start-up or setting update, the
following was detected.
 When "When the number of
saved files exceeds the above
set value: Stop" has been set in
the logging setting, logging was
stopped since the set number of
saved files was reached.
At other than start-up or setting
update, the following was
detected.
 When "When the number of
saved files exceeds the above
set value: Stop" has been set in
the logging setting, logging was
stopped since the set number of
saved files was reached.
The queue for e-mail or FTP
transmission has become full.
Processing is not available since a
module stop error is on.
(From the previous page)
Corrective action
 By FTP operation (refer to
Section 6.7), delete unnecessary
files to secure a free space in the
standard ROM or CF card.
 Check the CF card. (Refer to
Section 9.1 (9).)
 By FTP operation (refer to
Section 6.7), delete unnecessary
files to secure a free space in the
standard ROM or CF card.
 Check the CF card. (Refer to
Section 9.1 (9).)
 By FTP operation (refer to
Section 6.7), delete unnecessary
files to secure a free space in the
standard ROM or CF card.
 Check the CF card. (Refer to
Section 9.1 (9).)
 Delete logging files by FTP
operation (refer to Section 6.7) or
LOGDEL instruction (refer to
Section 8.7).
 Reduce the frequency of e-mail
or FTP transmission.
 Remove causes of the module
stop error and reset the CPU
module.
(Continued on the next page)
MELSEC-Q
Error type
Stop
Continue
Stop
Continue
Stop
Continue
Stop
Continue
Continue
Stop
9 - 29