9 TROUBLE SHOOTING
Error
Error name
code
Duplicate high speed
064Ah
logging specification
error
Excessive number of
064Bh
device points for high
speed sampling tag
High speed sampling
064Ch
tag component
registration error
High speed sampling
064Dh
tag specification error
High speed logging
064Eh
specification error
No specified event
064Fh
error
High speed sampling
0650h
tag CPU specification
error
High speed logging
0651h
storage setting error
Network
0659h
communication route
error
Unsupported CPU
065Ah
error
9 - 36
Error definition
There are more than one logging
setting in which high speed
sampling tag is specified. The
logging setting file is corrupted.
Total device points of the high
speed sampling tag exceeds 96
points.
Failed to register the component
device of the high speed sampling
tag to the control CPU.
The high speed sampling tag was
specified in the TAG instruction.
The high speed sampling logging
was specified in the LOG
instruction.
The event specified in the logging
setting does not exist or the event
monitor setting was deleted.
The CPU of other than the
access target CPU setting No. 1
was specified for the component
of the high speed sampling tag,
or the tag setting file is corrupted.
"Standard ROM" was selected in
[Save in] of the high speed
logging.
A nonexistent module was
specified for "Start I/O" in
"Network communication route" in
Access target CPU setting.
A CPU that is not supported by
GX RemoteService-I exists as an
access target CPU.
(From the previous page)
Corrective action
 Check the logging setting.
(Refer to Section 6.4.4)
 Initialize the module (refer to
Section 4.13) and then make the
tag setting (refer to Section 6.3.3)
again.
 Check the component setting of
the high speed sampling tag
(refer to Section 6.3.3) and make
setting so that the total device
points do not exceed 96 points.
 Create or increase a user setting
system area by GX Developer.
(Refer to Section 6.3.3
REMARKS.)
 For redundant CPUs, check their
system areas in both systems.
 Check the control data of the
TAG instruction. (Refer to
Section 8.5.)
 Check the control data of the
LOG instruction. (Refer to
Section 8.6.)
 Specify an existing event.
 Initialize the module (refer to
Section 4.13) and then make the
tag setting (refer to Section 6.3.3)
again.
 Select the CF card.
 Correct the start I/O address in
Access target CPU setting.
 Do not use GX RemoteService-I.
 Do not access the Universal
model QCPU and C Controller
module.
(Continued on the next page)
MELSEC-Q
Error type
Stop
Stop
Stop
Display
Display
Stop
Stop
Stop
Continue
Stop/
Continue
9 - 36