6 FUNCTIONS
6.6.4 E-mail transmission by programmable controller CPU
ZP.WMSEND
Web server module
6 - 79
This section explains the WMSEND instruction used to send e-mail with a sequence
program.
1)
2)
3)
(S1)
(S2)
"Un"
Destination No.
Tag/Logging No
I/O No.
File name.
1) Head I/O number of Web server module
2) Control data (Transmission destination No., tag/logging No, file name, etc.)
Set a destination e-mail address preset in the e-mail setting, an attached
tag/logging data or user data file, etc.
3) Transmission data (Subject + main text)
Character data set in the sequence program are used.
Since character data is not converted into the ASCII text format, set them as ASCII
characters in the sequence program.
4) Completed bit
5) Main text of e-mail
Character data set in the sequence program are used.
Since character data is not converted into the ASCII text format, set them as ASCII
characters in the sequence program.
The following binary coded data is handled as control codes.
0D0A
: Linefeed code CR + LF
H
00
: End of main text
H
6) Attached file
Tag data/logging data/user data file
4)
(D)
Subject + Main text
5) Main text
MELSEC-Q
Mail server
6) Attached file
Tag/logging
(.BIN/.CSV)
data, user
data file
6 - 79