Mitsubishi Electric MELSEC Q Series User Manual page 444

Programmabale web server module
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

8 DEDICATED INSTRUCTION
Control data
Device
Item
(S1) + 0 Execution type
Completion
(S1) + 1
status
Number of data
(S1) + 2
to be written
Write result
(S1) + 3
(Number of
data)
(S1) + 4
File position
(S1) + 5
Number of
(S1) + 6
columns
specification
Word/byte
(S1) + 7
specification
(S1) + 8
to
File name
(S1) + 13
8 - 26
Specify the execution type.
0000
: Binary write
H
0100
: CSV format conversion write
H
The status of the instruction completion is stored.
0
: Normal completion
Other than 0 : Abnormal completion (Error code) ( 2)
Specify the number of data to be written. (Word unit)
When specifying the byte unit in (S1)+7, also set the number of data in
word units by converting it into word units.
With respect to the data specified in (S2), the number of actually written
data enters here.
• The unit depends on the word/byte specification.
Set the file position where data will be written.
• When binary write is specified in (S1)+0
00000000
H
00000001
to FFFFFFFE
H
FFFFFFFF
H
• When CSV format conversion write is specified in (S1)+0
00000000
to FFFFFFFE
H
FFFFFFFF
H
• When binary write is specified in (S1)+0
Always specify "0".
• When CSV format conversion write is specified in (S1)+0
Specify the number of columns where data will be written.
0
: Number of columns not specified. Written to 1 row.
Other than 0 : Written to the specified number of columns.
Specify the word or byte unit.
0 : Word
1 : Byte
Specify a file name with a character string.
• Specify a name (8 characters) + period + extension (3 characters)
within the specified number of characters.
• When omitting an extension, also omit a period (".").
Setting data
: Written to the file, starting at its
beginning.
: Written to the file, starting at the
H
specified position.
The unit depends on the word/byte
specification.
: Added to the end of the file.
: Written to the file, starting at its
H
beginning.
: Added to the end of the file.
MELSEC-Q
Setting
Setting side
range
( 1)
0000
H
User
0100
H
System
1 to 480
User
System
0
User
to
FFFFFFFF
H
0
to
User
65535
0, 1
User
String
User
8 - 26

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec qj71ws96

Table of Contents