12 Option -JC24X
12.3
12.3.1 Technical data
INFO
96
Digital Inputs
Technical Data - Digital Inputs
16 digital inputs
Type
Input terminals
LEDs, inputs 1-16
Heat loss of logic circuit
Rated input voltage
Voltage range
Input current typically
Input resistance
Input delay time
Signal voltage ON
Signal voltage OFF
Signal processing
Electrical isolation
All digital inputs and outputs have got the same reference potential.
A digital output may directly (without additional load) be connected to a digital
input.
DC 24 V -15 % ... +20 %
PNP
Plug-in terminal blocks
24 volt are applied to the input.
The LEDs are only lit, if the JM-D203
-JC24X is connected to the voltage supply.
0.3 Watts
DC 24 V -15 % ... +20 %
0 ... 30 V
Approx. 7.5 mA
3.0 kΩ
approx. 3 ms (from 0 to 1, and from 1 to 0)
17 V min.
5 V max.
Dynamic
Electrical isolation to logic is available
Jetter AG