Figure 114: Cover Retention Screws
Note: If any drives were removed earlier to facilitate the removal of the chassis, follow the
rest of the steps to reinstall the drives by following the labeling scheme noted earlier. If not,
proceed to the cabling section.
Step 26 : If the chassis is being installed into a rack that will be shipped fully assembled, you must install
eight (four per side) of the included M5 x 12mm T15 Flat Head Torx screws into the two brackets
at the front of the chassis in the following locations. These screws should be tightened to
3.38-3.61 Nm / 30-32 in-lbf using a Long T15 Torx Screwdriver. If this chassis will not be installed
into a rack for shipping purposes, skip this step and move on to the next one.
Figure 115: Shipping Bracket Screw Locations
Step 27 : Install the 3.5in HDD Assembly.
3. Support
3.8 Rails Replacement
110