Part 5: Review on Replacement of MR-J3-DU_ with MR-J4-DU_

3.2 Magnetic contactor control connector (CNP1)

CAUTION
By enabling magnetic contactor drive output, the main circuit power supply can be shut off automatically
when an alarm occurs in the converter unit or the drive unit.
To enable magnetic contactor drive output, set [Pr. PA02] of the converter unit to "_ _ _ 1" (initial value).
(1) When magnetic contactor drive output is enabled
To control the magnetic contactor, connect the magnetic contactor control connector (CNP1) to the coil
of the magnetic contactor.
Always connect the magnetic contactor wiring connector to the converter unit. If
the connector is not connected, an electric shock may occur since CNP1-1 and
L11 are always conducting.
[Pr. PA02]
0 0 0
1
Internal connection diagram of CNP1
Power
supply
(Note 1)
malfunction
Note 1. A step-down transformer is required when coil voltage of the magnetic contactor is
200 V class, and the converter unit and the drive unit are 400 V class.
2. The bus voltage decreases depending on the main circuit voltage and operation
pattern, which may cause the forced stop deceleration to shift to the dynamic
brake deceleration. When dynamic brake deceleration is not required, delay the
time to turn off the magnetic contactor.
3. When the voltage between L11 and L21 drops due to an instantaneous power
failure and others, the magnetic contactor is turned off.
Magnetic contactor drive output selection
0: Disabled
1: Enabled
(Note 2, 3)
MCCB
MC
MC1
MC2
Drive unit
Converter unit
Emergency stop
malfunction
RA1
RA2
5 - 9
Converter unit
L1
L2
L3
L11
L21
CNP1
1
2
Operation ready
switch
OFF/ON
MC
SK