8.12.10 Data Set 93 - Writing a Command

Structure of the command data set
ID No.: Coding
1-byte commands
0
0
Reserved
703
1
Trip reset
713
2
Emergency start ON
714
3
Emergency start OFF
709
4
Automatic operating mode Transition to automatic operating mode (DP master controlled)
710
5
Operating mode manual
711
- bus
712
- operation local
701
6
Factory settings
704
7
Delete maximum pointer
705
13
Log list -
delete trippings
706
14
Log list -
delete events
702
9
Restart
707
10
Parameterization disable
CPU/master ON
708
11
Parameterization disable
CPU/master OFF
Table 8-26: Data set 93 - writing a command
SIRIUS 3RW44 System Manual
GWA 4NEB 535 2195-02 DS 04
Byte
Meaning
Preamble
0
Coordination
1 - 3
Reserved
Command
4
Number of commands
5
Command 1
6
Command 2
7
Command 3
8
Command 4
9
Command 5
Table 8-25: Structure of the command data set
Command
No function
Reset and acknowledgement of error messages
Switch on emergency start
Switch off emergency start
Transition to manual operating mode. The soft starter switches to
manual bus or manual operation local operating mode, independent of
which interface received the command.
Restore factory settings of the parameters.
The measured values for the preventive diagnosis are deleted (=0).
Delete log list with recorded causes of errors.
Delete log list with recorded warning messages and certain actions.
Trigger restarting (same as after line ON), e.g. after reassigning the
station address.
No parameterization possible via the parameterizing master or this
master's parameters are ignored.
Parameterization possible via the parameterizing master.
PROFIBUS DP Communication Module
Comment
Writing 0x20 via channel C1 (PLC)
Writing 0x30 via channel C2 (PC)
Writing 0x40 via device interface (PC)
Value range 1 ... 5
Number of subsequent valid commands
For the consecutive number refer to the table below
Optional (for coding refer to the table below)
Optional (for coding refer to the table below)
Optional (for coding refer to the table below)
Optional (for coding refer to the table below)
Meaning