Settable (User Definable) Signals - AUMA AUMATIC AC 01.2 Manual

Profibus dp actuator controls
Hide thumbs Also See for AUMATIC AC 01.2:
Table of Contents

Advertisement

Commissioning
3.6.2.

Settable (user definable) signals

Table 2: Description of the parameter settings
Prm-Text-Def GSD file
(0) = "Bit: Reserved"
(1) = "Bit: End p. CLOSED"
(2) = "Bit: End p. OPEN"
(3) = "Bit: End p. CLOSED, blink"
(4) = "Bit: End p. OPEN, blink"
(5) = "Bit: Setpoint reached"
(6) = "Bit: Running CLOSE"
(7) = "Bit: Running OPEN"
(8) = "Bit: Selector sw. LOCAL"
(9) = "Bit: Sel. sw. REMOTE"
(10) = "Bit: Sel. sw. OFF"
(11) = "Bit: Limit sw. CLOSED"
(12) = "Bit: Limit sw. OPEN"
(13) = "Bit: Torque sw. CLOSE"
(14) = "Bit: Torque sw. OPEN"
(15) = "Bit: Device ok"
(16) = "Bit: Failure"
(17) = "Bit: Function check"
(18) = "Bit: Out of spec."
(19) = "Bit: Maintenance requ."
12
Designation
(process representation)
Bit: End p. CLOSED
Bit: End p. OPEN
Bit: EP CLOSED, blink
Bit: EP OPEN, blink
Bit: Setpoint reached
Bit: Running CLOSE
Bit: Running OPEN
Bit: Sel. sw. LOCAL
Bit: Sel. sw. REMOTE
Bit: Sel. sw. OFF
Bit: Limit sw. CLOSED
Bit: Limit sw. OPEN
Bit: Torque sw.CLOSE
Bit: Torque sw.OPEN
Bit: Device ok
Bit: Failure
Bit: Function check
Bit: Out of spec.
Bit: Maintenance requ.
AC 01.2/ACExC 01.2 Profibus DP
Description
For limit seating: Limit switch operated in direction CLOSE
For torque seating: Torque switch and limit switch operated
in direction CLOSE
For limit seating: Limit switch operated in direction OPEN
For torque seating: Torque switch and limit switch operated
in direction OPEN
End position CLOSED reached or intermediate position
reached
(The intermediate position is only indicated if parameter
Signal interm. pos. M0167 = OPEN/CLOSED = On.)
Signal blinking: Actuator runs in direction CLOSE.
End position OPEN reached or intermediate position
reached.
(The intermediate position is only indicated if parameter
Signal interm. pos. M0167 = OPEN/CLOSED = On.)
Signal blinking: Actuator runs in direction OPEN.
The position setpoint is is within max. error variable (outer
dead band). Is only signalled if Profibus DP master has set
the Fieldbus SETPOINT bit (process representation output).
An operation command in direction CLOSE is performed
via fieldbus: Fieldbus CLOSE or Fieldbus SETPOINT (pro-
cess representation output).This bit remains also set during
operation pauses (e.g. due to the dead time or the reversing
prevention time).
An operation command in direction OPEN is performed via
fieldbus: Fieldbus OPEN or Fieldbus SETPOINT (process
representation output). This bit remains also set during op-
eration pauses (e.g. due to the dead time or the reversing
prevention time).
Selector switch is in position LOCAL.
Selector switch is in position REMOTE.
Selector switch is in position OFF.
Limit switch operated in end position CLOSED
Limit switch operated in end position OPEN
Torque switch operated in direction CLOSE
Torque switch operated in direction OPEN
Collective signal 05:
The device is ready for remote control.
No AUMA warnings, AUMA faults or signals according to
NAMUR are present.
Collective signal 10:
Indication according to NAMUR recommendation NE 107
Actuator function failure, output signals are invalid.
Collective signal 08:
Indication according to NAMUR recommendation NE 107
The actuator is being worked on; output signals are tempor-
arily invalid.
Collective signal 07:
Indication according to NAMUR recommendation NE 107
Actuator is operated outside the normal operation conditions.
Collective signal 09:
Indication according to NAMUR recommendation NE 107
Recommendation to perform maintenance.
Actuator controls