Process Representation Output; Transmitting Operation Commands To Or Reading Out From The Actuator Using Register Functions; Description Of The Output Data - AUMA AM 01.1 Operation Instructions Manual

Hide thumbs Also See for AM 01.1:
Table of Contents

Advertisement

Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Modbus

10. Process representation output

10.1 Transmitting operation commands to or reading out from the actuator using register functions

Offset
(hexadecimal)
0x1000
0x1002
Holding register operation commands also change the corresponding coils for operation commands.
Operation commands which cannot be executed are rejected with ILLEGAL DATA VALUE (code 03). Operation commands
cannot be executed if a thermal fault or mains failure have occurred, or if the local controls are not set to remote, or if
commands are contradictory.
If a thermal fault or a mains failure occurs during remote operation, or if the remote operation is switched off via the selector
switch, the actuator will cancel all pending operation commands

10.2 Description of the output data

Register 1: Commands (high byte)
With the bits 0 – 2, the opera-
tion commands are transmit-
ted to the actuator. Only one of
these bits may be set at any
given
time.
SETPOINT is set, the value of
the nominal position
(register 2) is used.
Bits 3 – 15 are reserved for fu-
ture extensions and must re-
main set to 0.
As soon as these bits are writ-
ten to via coil functions, the
contents of the respective
Holding Registers for the op-
eration commands will also
change.
If the Coil Remote SETPOINT
is
used,
the
setpoint has to be entered on
the setpoint register.
32
Via the process representation output, the master (controls) can control the
slave (actuator).
Functions to be used:
Preset Single Register (06); Preset Multiple Register (16);
Read Holding Register (03)
Offset
Register contents
(decimal)
Register 1: Commands
4096
Bit
Bit
15
14
Register 2: E1 Setpoint
4098
Bit Designation
Remote
0
If
remote
Remote
1
CLOSED
Remote
2
SETPOINT
3
4
5
respective
6
7
Bit
Bit
Bit
Bit
Bit
Bit
13
12
11
10
9
8
Value Description
1
Running OPEN
OPEN
0
Not running OPEN
1
Running CLOSE
0
Not running CLOSE
Running to setpoint
1
Can only be set if a position transmitter e.g. potentiom-
eter/ RWG (options) is available.
0
Not running to setpoint.
1
- -
Not assigned (reserved for extensions)
0
1
- -
Not assigned (reserved for extensions)
0
1
- -
Not assigned (reserved for extensions)
0
1
- -
Not assigned (reserved for extensions)
0
1
- -
Not assigned (reserved for extensions)
0
Operation instructions
Bit
Bit
Bit
Bit
Bit
Bit
Bit
7
6
5
4
3
2
1
Bit
0