AC 01.2/ACExC 01.2
Function not active
Function active
8.6.2.

Operation mode for stepping mode

Off
Remote
Local
Remote and local
Information
8.6.3.

Start and end of stepping mode

8.6.4.

On times and off times

Device configuration M0053
Application functions M0178
Activation M0212
Timer CLOSE M0156
Timer OPEN M0206
Default value: Function not active
Setting values:
Function <Stepping mode> deactivated.
Function <Stepping mode> activated.
Stepping mode can be activated via operation modes Local and/or Remote.
Customer settings M0041
Timer M0142
Step mode CLOSE M0157
Step mode OPEN M0207
Default value: Off both directions
Setting values:
Stepping mode is switched off.
Stepping mode is active in the operation modes: Remote, Remote II, Fieldbus
Stepping mode is active in the operation modes: Local, Service
Stepping mode is active in the operation modes: Remote, Remote II, Fieldbus, Local,
Service
The timer cannot be by-passed in <Operation mode EMERGENCY>.
Start and end of stepping mode can be individually set for both directions.
Customer settings M0041
Timer M0142
End stepping CLOSE M0152
Start stepping CLOSE M0153
Start stepping OPEN M0154
End stepping OPEN M0155
Default values:
End stepping CLOSE = 0.0 %
Start stepping CLOSE = 100.0 %
Start stepping OPEN = 0.0 %
End stepping OPEN = 100.0 %
Setting ranges:
End stepping CLOSE = 0.0 – 99.9 %
Start stepping CLOSE = 0.1 – 100.0 %
Start stepping OPEN = 0.0 – 99.9 %
End stepping OPEN = 0.1 – 100.0 %
On or off times can be set individually for directions OPEN and CLOSE.
Customer settings M0041
Timer M0142
On time CLOSE M0163
Off time CLOSE M0164
Application functions