Operation; Operation Mode Off; Operation Mode Local; Push-To-Run Operation Or Self-Retaining Local - AUMA AC 01.2 Manual

Actuator controls
Hide thumbs Also See for AC 01.2:
Table of Contents

Advertisement

Operation

6.
Operation
6.1.

Operation mode Off

Characteristics
6.2.

Operation mode Local

Properties
6.2.1.

Push-to-run operation or self-retaining Local

Off (push-to-run op.)
OPEN
CLOSE
30
Different operation modes (states) are available. The current operation mode is
indicated in the first line of the display:
Figure 31: Example: Operation mode Off
This chapter describes the characteristics of the different operation modes; the
respective functions are described in separate chapters.
The selector switch is in position 0 (OFF).
The indication in the top row of the display shows: Off
Electric operation is not possible (not even EMERGENCY operation).
The controls remain fully operative as far as signalling is concerned (controls'
power supply is maintained).
Push buttons
C can be used for menu navigation via the display.
Selector switch is in position Local control (LOCAL).
The indication in the top row of the display shows: Local
In motor operation, the actuator can be controlled locally via the push buttons
(OPEN), STOP,
Faults and warnings without automatic reset can be confirmed with the push
button RESET.
Parameter Self-retaining Local M0076 determines the actuator operation behaviour
to operation commands via push buttons on local controls.
Customer settings M0041
Local controls M0075
Self-retaining Local M0075
Default value: OPEN and CLOSE
Setting values:
Push-to-run operation activated, self-retaining off:
Actuator only runs in directions OPEN or CLOSE while an operation command is
being received. The actuator stops if the operation command is cancelled.
In direction OPEN = self-retaining (in direction CLOSE push-to-run operation):
After an operation command in direction OPEN, the actuator continues to run, even
if the operation command is cancelled (self-retaining). The actuator is either stopped
by the STOP command or if end position OPEN or an intermediate position OPEN
has been reached.
In direction CLOSE = self-retaining (in direction OPEN push-to-run operation):
(CLOSE).
Actuator controls
AC 01.2/ACExC 01.2 Profinet