Appendix; Selection Overview For Output Contacts And Indication Lights (Digital Outputs Dout) - AUMA AC 01.2 Manual

Actuator controls
Hide thumbs Also See for AC 01.2:
Table of Contents

Advertisement

Actuator controls
AC 01.2/ACExC 01.2
16.

Appendix

16.1.

Selection overview for output contacts and indication lights (digital outputs DOUT)

Table 21:
Signal
Not used
End position CLOSED
End position OPEN
End p. CLOSED, blink
End p. OPEN, blink
Setpoint pos.reached
Running CLOSE
Running OPEN
Selector sw. LOCAL
Selector sw. REMOTE
Selector sw. OFF
Limit switch CLOSED
Limit switch OPEN
Torque sw. CLOSED
Torque sw. OPEN
NAMUR failure
NAMUR funct. check
NAMUR out of spec.
NAMUR mainten. req.
Fault
Warning
Not ready REMOTE
Operation pause active
Start stepping mode
Depending on the version, the AC is equipped with up to 12 output contacts (digital
outputs).
Description
End position CLOSED reached
Indication depends on the type of seating and means either
limit seating, end position CLOSED reached, or
torque seating, end position CLOSED reached
End position OPEN reached
Indication depends on the type of seating and means either
limit seating, end position OPEN reached, or
torque seating, end position OPEN reached
End position CLOSED reached or intermediate position reached
(The intermediate position is only indicated if parameter Signal interm. pos. M0167 =
OPEN/CLOSED = On.)
Signal blinking: Actuator runs in direction CLOSE.
End position OPEN reached or intermediate position reached.
(The intermediate position is only indicated if parameter Signal interm. pos. M0167 =
OPEN/CLOSED = On.)
Signal blinking: Actuator runs in direction OPEN
The position setpoint is is within max. error variable (outer dead band).
Actuator runs in direction CLOSE.
Actuator runs in direction OPEN.
Selector switch is in position LOCAL.
Selector switch is in position REMOTE.
Selector switch is in position OFF.
Limit switch operated in direction CLOSE
Limit switch operated in direction OPEN
Torque in direction CLOSE exceeded
Torque in direction OPEN exceeded
Collective signal 10:
Indication according to NAMUR recommendation NE 107
Actuator function failure, output signals are invalid.
Collective signal 08:
Indication according to NAMUR recommendation NE 107
The actuator is being worked on; output signals are temporarily invalid.
Collective signal 07:
Indication according to NAMUR recommendation NE 107
Difference between setpoint and actual value is too important (exceeding the normal operation
conditions).
Collective signal 09:
Indication according to NAMUR recommendation NE 107
Recommendation to perform maintenance.
Collective signal 03:
Contains the result of a disjunction (OR operation) of all faults.
Collective signal 02:
Contains the result of an OR disjunction of all warnings.
Collective signal 04:
Contains the result of a disjunction (OR-operation) of the signals, forming the "Not ready
REMOTE" group.
The actuator cannot be operated from REMOTE.
The actuator can only be operated via the local controls.
Actuator is in pause time of stepping mode
The actuator is within the set stepping range.
Appendix
133