Power Jumper Contacts/Field Supply; Figure 3: Power Jumper Contacts; Table 4: Legend For Figure "Power Jumper Contacts - WAGO 750-429/040-001 Manual

2-channel digital input; 60 v dc; 3 ms; extreme for wago-i/o-system 750 xtr
Table of Contents

Advertisement

18
Device Description
3.2.2

Power Jumper Contacts/Field Supply

Risk of injury due to sharp-edged blade contacts!
The blade contacts are sharp-edged. Handle the I/O module carefully to prevent
injury. Do not touch the blade contacts.
The I/O module 750-429/040-001 has 2 self-cleaning power jumper contacts that
supply and transmit power for the field side. The contacts on the left side of the
I/O module are designed as blade contacts and those on the right side as spring
contacts.

Figure 3: Power Jumper Contacts

Table 4: Legend for Figure "Power Jumper Contacts"

Contact
1
2
3
4
Do not exceed maximum values via power contacts!
The maximum current that can flow through the power jumper contacts is 10 A.
The power jumper contacts can be damaged and the permissible operating
temperature can be exceeded by higher current values.
When configuring the system, do not exceed the permissible maximum current
value. If there is a higher power requirement, you must use an additional supply
module to provide the field voltage.
Manual
Version 1.2.0
Type
Function
Spring contact Potential transmission (U
Spring contact Potential transmission (0 V) for field supply
Blade contact
Potential feed-in (0 V) for field supply
Blade contact
Potential feed-in (U
WAGO-I/O-SYSTEM 750 XTR
750-429/040-001 2DI 60V DC 3ms XTR
) for field supply
v
) for field supply
v