MAINTENANCE INSTRUCTIONS
• Thread the connector through the cable gland in the plastic
housings. It is recommended that the cable gland inside the
cooler is unscrewed from the housing to provide better access
when passing the connector through it.
• Remove the four brackets that clamp the motor to the venturi.
• The motor can now be removed from the cooler and replaced.
Use a philips head screwdriver.
• Reverse the above steps to re-assemble the new motor.
• Note! Ensure excess cable length is secured to the internal
conduit to prevent it being drawn into the fan.
• When fitting the fans back on to the motor shaft, align the flat
on the shaft with the grub screw. Push the fan into the Venturi
up to a dead stop on the shaft. The fan and the Venturi should
be aligned.
ACCESSING THE SOLENOID, CHLORINATOR, PROBE
OR DRAIN PUMP
Purpose:
To replace a faulty component.
Method:
• Turn off Power to the cooler.
• Turn off the water supply to the solenoid valve
• Remove the water supply from the solenoid valve.
• Remove the solenoid valve access cover by removing the
three screws. Note! Do not remove the screw in the middle of
the cover.
ILL3559-A
ILL3559-A
• Rotate the solenoid valve opening/close past the supporting
tab, ready to remove it thought the square opening.
ILL3560-A
• Pull to remove the solenoid valve from the cooler.
ILL3560-A
• Re-position the grommet in to the hole in the plastic housing.
• Examine the solenoid valve for blockages before deciding that
it will need to be replaced.
• Remove the utilities cover to gain access to the inside of the
cooler.
ILL3561-A
ILL3561-A
SEELEY INTERNATIONAL - INSTALLATION MANUAL CW-P15 859740-G |
ILL3562-A
ILL3562-A
ILL3563-A
ILL3563-A
ILL3564-A
ILL3564-A
ILL3534-A