7.8.3
Setting station address via 3RW5 HMI Standard
Requirements
● 3RW51 soft starter
● Unlocked locking switch on the 3RW5 HMI Standard
● Control priority is with the 3RW5 HMI Standard
Procedure
1. Select the menu item "PBADR".
The currently set station address is displayed. You will find more information on operating
the 3RW5 HMI Standard in the Equipment Manual of the 3RW5 soft starter.
2. Hold down a navigation button until the ">" symbol appears before the currently set
station address.
The ">" symbol denotes the processing status of the station address.
3. Press a navigation button.
The first position of the station address runs through the potential digits (0 ... 1).
4. Press a navigation button when the desired digit appears.
This sets the first digit of the station address. The second position of the station address
runs through the potential digits (0 ... 9, depending on the first digit).
5. Press a navigation button when the desired digit appears.
This sets the second digit of the station address. The third position of the station address
runs through the potential digits (0 ... 9, depending on the second digit).
6. Press a navigation button when the desired digit appears.
You have set the station address and are in the "PBADR" menu item. The ">" symbol to
denote the processing state is grayed out.
3RW51 Soft Starter
Manual, 06/2019, A5E37108631002A/RS-AB/002
Functions
7.8 3RW5 HMI Standard
99