4.4
Connecting the external bypass contactor to the 3RW51 soft starter
Requirements
● Observe the conductor cross-sections and tightening torques in the data sheet or on the
front beneath the hinged cover.
● Pay attention to the required tools indicated on the front beneath the hinged cover.
Size
Size 1 / 2
Size 3
Size 4
Procedure for screw connection - size 2
● Connect connection 7 / B1, 8 / B2, 9 / B3 to the supply system
screws
● Repeat steps
3RW51 Soft Starter
Manual, 06/2019, A5E37108631002A/RS-AB/002
4.4 Connecting the external bypass contactor to the 3RW51 soft starter
Article number
3RW5.1.-....
3RW5.2.-....
3RW5.3.-....
3RW5.4.-....
.
+
for connection 2 / T1, 4 / T2, 6 / T3 with the motor.
Tightening torque
4.5 ... 6 Nm
10 ... 14 Nm
14 ... 24 Nm
and tighten the
Wiring
59