A.3.3
EMERGENCY STOP shutdown to SIL 3 or PL e with a 3SK1 safety relay
The 3RW51 soft starter has no effect or influence on the safety function of the application.
For this reason, it is neither positively nor negatively considered in the safety application, and
also does not have to be included in the calculation for proof according to the standards.
Safe shutdown up to SILCL 3 according to IEC 62061:2005 / PL e according to EN ISO
13849-1:2015 requires the use of 2 redundant contactors and monitoring of the auxiliary
contacts of both contactors. Two-channel monitoring of the EMERGENCY STOP is also
required here.
Basic configuration
3RW51 Soft Starter
Manual, 06/2019, A5E37108631002A/RS-AB/002
Emergency stop
3TS contactor
3RW51 soft starter
3TS contactor
Motor
3SK1 safety relay
Example circuits
A.3 Special applications