3.5.5
Installing the 3RW5 HMI Standard in the control cabinet door
Requirements
● Note the mounting positions, minimum clearances and ambient conditions stated on the
data sheet
● 3RW5 HMI Standard (accessories)
● An HMI connecting cable (accessory) of suitable length
● Cutout of suitable size in the control cabinet door
● PZ2 screwdriver in installation with door mounting kit IP65
● Device depth of the 3RW5 HMI Standard:
– Total depth: 32 mm
– Embedded depth: 29 mm
● Permissible wall thickness of the cabinet door:
– Without IP65 door mounting kit: 1.5 to 3.0 mm
– With IP65 door mounting kit: 1.0 to 7.0 mm
● Optional accessories:
– IP65 door mounting kit
Procedure without door mounting kit IP65
Place the 3RW5 HMI Standard into the cutout of the control cabinet door
3RW5 HMI Standard engages audibly in 4 fixtures
3RW51 Soft Starter
Manual, 06/2019, A5E37108631002A/RS-AB/002
Mounting and Dismantling
3.5 Installing / mounting / removing 3RW5 HMI
.
. Ensure that the
41