7.9.4.2
Monitoring the process image of the 3RW51 soft starter with the 3RW5 HMI High
Feature
Requirements
You are in menu "Monitoring > Process Image".
Procedure
In the process image of the inputs (PII) and outputs (PIQ), you can see which bits of the
process image are active or inactive.
7.9.5
Parameterizing analog output AQ via the 3RW5 HMI High Feature
You can re-parameterize the output of the analog output with the High Feature 3RW5 HMI
High Feature.
The actual average phase current L1 - L3 of the motor is displayed in % at the evaluation
unit via the analog output. Depending on the respective connecting terminal being used, the
signal can be displayed either as current or voltage.
● Terminals: AQ- / AQ I+
Measuring range of current output: 4 - 20 mA
● Terminals: AQ- / AQ U+
Measuring range of voltage output: 0 - 10 V
Requirements
● Access protection to 3RW5 HMI High Feature is not active or has been reset
● Device version with analog output
● Evaluation unit is connected properly (Page 167)
● You are in menu "Parameters > Soft Starter > Analog Output".
3RW51 Soft Starter
Manual, 06/2019, A5E37108631002A/RS-AB/002
Checkbox
7.9 3RW5 HMI High Feature
Status
inactive
active
Functions
Bit
0
1
109