4.3
Connecting 3RW51 soft starter to main circuit connection (line side /
motor side)
Requirements
● Observe the conductor cross-sections and tightening torques in the data sheet or on the
front beneath the hinged cover
● Pay attention to the required tools indicated on the front beneath the hinged cover
● When using a busbar connection (sizes 3 and 4), you require wrenches of width A/F of 13
and 17.
Size
Size 1 / 2
Size 3
Size 4
Procedure for screw connection - size 2
Hazardous voltage.
Will cause death or serious injury.
Turn off and lock out all power supplying to this device before working on this device.
3RW51 Soft Starter
Manual, 06/2019, A5E37108631002A/RS-AB/002
4.3 Connecting 3RW51 soft starter to main circuit connection (line side / motor side)
DANGER
Article number
3RW5.1.-....
3RW5.2.-....
3RW5.3.-....
3RW5.4.-....
Tightening torque
4.5 ... 6 Nm
10 ... 14 Nm
14 ... 24 Nm
Wiring
57