Siemens 3RW51 Series Manual page 71

Industrial controls , soft starters and solid-state switching devices

Advertisement

5.2
Overview of parameters
Parameters
Trip class for motor
overload protection
Rated operational current I
of the motor
1)
Current limiting value as a
multiple of the set rated
operational current I
of the
e
motor
Ramp-up time
Starting voltage
Ramp-down time
Soft Torque
RESET MODE
The rated operational current I
1)
specification of the manufacturer.
For meaning of scale, refer to inscription table in front panel of device.
2)
3RW51 Soft Starter
Manual, 06/2019, A5E37108631002A/RS-AB/002
Symbol
e
of the motor may, according to the standard, deviates by 20% from the rating plate
e
Setting range
10A, 10E, 20E, OFF
1 ... 16
2)
1.3 ... 7 x I
e
Max.
0 ... 20 s
If parameter value "0" is set, the motor
is switched on with a ramp-up time of
approx. 100 ms.
30 ... 100 %
0 ... 20 s
Off (LED off)
On (LED on)
Manual RESET (LED off)
Remote RESET (LED flashes green)
Auto RESET (LED lit green)
Parameter assignment
5.2 Overview of parameters
Factory setting
10A
16
4 x I
e
10 s
30 %
0 s
Off
Manual RESET
71