Siemens 3RW51 Series Manual page 182

Industrial controls , soft starters and solid-state switching devices

Advertisement

Example circuits
A.3 Special applications
A.3.4
Contactor for emergency start
Requirements
● Soft starting is not possible.
Automatic restart.
Can cause death or serious injury.
If a starting command is pending, a restart will be triggered automatically after the reset.
This particularly applies if the motor protection has tripped.
Dangerous states of the system can result.
Reset the start command (e.g. via the PLC or switch) before performing a reset.
To do this, for example, link the group error output (terminals 95 and 96) into the control.
182
WARNING
Manual, 06/2019, A5E37108631002A/RS-AB/002
3RW51 Soft Starter