3. Commissioning
3.3

Preparing the CTEL system for commissioning

3.3.1 Check the connected I-port devices

Festo P.BE-CPX-CTEL-EN en 1205NH
Note
Do not yet connect the CPX terminal to a higher-order con-
troller yet to prepare for commissioning.
You will thus avoid addressing errors which may occur in
various fieldbus systems when address ranges are modi-
fied during operation.
Please observe that host system integration of the CTEL mas-
ter module might have to take place through a device
description file, dependent on the CPX fieldbus node used.
You can find the corresponding description files at
www.festo.com.
Check, if necessary, the position of the DIL switches to
guarantee the desired operating mode and configuration
presetting.
Check the CTEL master module for a tight fit in the inter-
linking block.
Check whether the connected devices correspond to the
entry of the configuration file on the host system (see
section 2.6).
Check whether the connected I-port devices are distrib-
uted corresponding to their priority for the diagnostic/er-
ror messages at the I-ports (see section 4.2.1).
Check whether the current consumption of the connected
I-port device and the other CPX modules corresponds to
the specifications and limits (see section 2.5).
Check the power supply connections at the interlinking
blocks.