4. Diagnostics and error handling
CPX error
Description of possible causes
number
0
Device OK
General error
1
– Device NOK, general diagnostics
– Hardware error – device replacement
– Component error – repair or replace-
ment
– General error in power supply
– Fuse triggered
– Device software error
– Mass error
– Temperature overload
– Technology-specific application error
– measuring range exceeded
2
Short circuit
3
Wire break
Error in the power supply
5
– Primary voltage/main power supply
too low
– undervoltage PL Device supply (only
relevant if PL monitoring is active in a
device)
9
Below minimum value
– Device has fallen below temperature
limit
– Error in memory buffering
– Low battery level
10
Above maximum level
– Device has exceeded temperature limit
– Primary voltage/main power supply
too low
4-6
Error handling
No action required
Check device, eliminate errors
Check installation
Reset device
Check application
Check installation
Check installation
Check the power supply
Check installation
Check batteries
Check installation
Check the power supply