Page 2
Essential or useful accessories Information on environmentally sound usage Text designations: Activities that may be carried out in any order 1. Activities that should be carried out in the order stated – General lists Festo – P.BE-CPX-CTEL-EN – 1601b – English...
Page 4
..... . Commissioning with the Festo Maintenance Tool software (CPX-FMT) ....
Page 5
CPX terminal can be found in the CPX system description (è P.BE-CPX-SYS-...). Service Please consult your regional Festo contact if you have any technical problems. Festo – P.BE-CPX-CTEL-EN – 1601b – English...
The module described in this document has been designed exclusively for use in combination with CPX terminals from Festo. The CPX terminal and its connected modules are intended for installation in ma chines and/or automated systems and may be used only as follows: –...
“Technical data” (è A.1 Technical data). The product-relevant EC directives can be found in the declar ation of conformity. Certificates and the declaration of conformity for this product can be found on the Festo website (è www.festo.com). Festo – P.BE-CPX-CTEL-EN – 1601b – English...
Short compressed air lines minimise the friction losses and the times for pressurising and exhausting the tubes. This enables smaller valves with sufficient flow to be used, thereby helping to reduce costs. Festo – P.BE-CPX-CTEL-EN – 1601b – English...
– Relay plates, pressure zone separation plates and blanking plates can also be integrated. I-Port input modules – Make available inputs for connecting sensors and enable inter rogation of cylinder positions, for example. Other I-Port modules Tab. 2.1 Festo – P.BE-CPX-CTEL-EN – 1601b – English...
Page 10
I-Port input module I-Port input module Fig. 2.2 A constant I/O data exchange takes place through the CTEL master module between the CPX terminal and the devices connected to the CTEL master module. Festo – P.BE-CPX-CTEL-EN – 1601b – English...
The CTEL master module has 4 I-Port interfaces. I-Port is an interface for the exchange of serial data for the connection of decentralised function modules (devices) from Festo at field level. It is based on the IO-Link technology and is compatible with it in certain areas.
Operation in accordance with the specifications is only guaranteed if original connecting cables from Festo are used. For operation in accordance with specifications, the maximum length of the I-Port con necting cables must always be observed (è 3.3 I-Port connecting cables). Festo – P.BE-CPX-CTEL-EN – 1601b – English...
– All 4 I-Ports are configured to “Port inactive” Lights up green Load voltage U (PL) present at all connected devices and is OK Flashes green At least one device reports undervoltage U (PL) (approx. 1 Hz) Festo – P.BE-CPX-CTEL-EN – 1601b – English...
Page 14
“OK” (LED illuminated green). The I-Port at which the error has occurred can be determined through the FMT/MMI using the diagnostic messages. Information on eliminating the displayed errors: è 5.2.2 Diagnostic/error messages by CPX error numbers. Festo – P.BE-CPX-CTEL-EN – 1601b – English...
24 bytes 24 bytes 32 bytes 32 bytes 1) Related to the complete CTEL master module Tab. 2.4 The I/O lengths listed here are the sum of the bytes available for all I-Ports together. Festo – P.BE-CPX-CTEL-EN – 1601b – English...
The I/O mode of the CTEL master module is set via DIL switch group 1 (è Tab. 2.5). The setting of the I/O length, i.e. the determination of available I/O bytes per I-Port, is implemented via DIL switch group 2 (è Tab. 2.6). Festo – P.BE-CPX-CTEL-EN – 1601b – English...
Page 17
24 bytes I/Os (6 bytes per I-Port) 32 bytes I/Os (8 bytes per I-Port) 1) Factory setting Tab. 2.6 The I/O length specified always applies for all 4 I-Ports (max. 8 bytes per I-Port). Festo – P.BE-CPX-CTEL-EN – 1601b – English...
Observe the handling specifications for electrostatically sensitive devices. Note Handle all modules and components carefully. Comply with the specified torques. Information on mounting the CPX terminal can be found in the CPX system description (è P.BECPXSYS…). Festo – P.BE-CPX-CTEL-EN – 1601b – English...
(è 2.5) before the CTEL master module is mounted, as these switches can no longer be reached after mounting. Electrical interface CPX-CTEL-4-M12-5POL Contact rails (CTEL master module) Screws Interlinking block (here with additional power supply, as an example) Fig. 3.1 Festo – P.BE-CPX-CTEL-EN – 1601b – English...
Operative malfunction due to impermissible cabling. To connect the I-Port devices to the CTEL master module, only use the special I-Port connecting cables from the Festo catalogue (è www.festo.com/catalogue) Observe the maximum length of 20 m for the I-Port connecting cables.
A total of up to 4 I-Port devices can be connected to one CTEL master module. The devices are connected to the CTEL master module via I-Port connecting cables from Festo (è 2.1 Overview of the CTEL system and 3.3 I-Port connecting cables).
The total current requirement of the CPX terminal and the CTEL system, as well as the limit values for the maximum current intensities, must be taken into account in the design of the voltage supply (è 3.5.2 Determining the current consumption). Festo – P.BE-CPX-CTEL-EN – 1601b – English...
Observe the instructions regarding selection of the power supply unit in the CPX system description (è P.BE-CPX-SYS-…). When using I-Port output modules with a separate load voltage connection, take into account the corresponding current consumption when selecting a power supply unit. Festo – P.BE-CPX-CTEL-EN – 1601b – English...
Page 24
2) Limit value within a voltage zone, minus the other consumers within the voltage zone Tab. 3.1 An additional power supply of 1.6 A per I-Port can be made available through the load voltage supply U Festo – P.BE-CPX-CTEL-EN – 1601b – English...
Otherwise, communication cannot be established and no diagnostic/error message is issued. Ensuring degree of protection IP65/67 Note To comply with degree of protection IP65/IP67: Seal unused I-Port interfaces with protective caps from the Festo catalogue (è www.festo.com/catalogue). Festo – P.BE-CPX-CTEL-EN – 1601b – English...
In cases in which the reserved address space is not completely used by the connected devices, this results in input and output addresses (channels) to which no device input or output is assigned. Festo – P.BE-CPX-CTEL-EN – 1601b – English...
3. If required: Parameterisation of the CTEL master module and the I-Port devices (è 4.6 Parameters). 4. Check power supplies (è 3.5 Connecting the power supply). 5. Commissioning of the entire system (è Description of the specific CPX bus node). Festo – P.BE-CPX-CTEL-EN – 1601b – English...
The integration of the CTEL master module into the host system might have to take place via a device description file, dependent on the CPX bus node used. Corresponding device description files can be found in the Festo Support Portal (è www.festo.com/sp). Check the CTEL master module and the connected I-Port devices ...
Moreover, additional diagnostic information relating to the CTEL master module is available, which can be called up via the fieldbus used as well as via the Festo Maintenance Tool (FMT) or the operator unit (MMI) (è 5.1 Summary of diagnostics options).
– Double-solenoid valves remain in the current position – Mid-position valves go into mid-position (pressurized, exhausted or closed, depending on valve type). Observe the product specific instructions in the documentation supplied with the valve terminal components. Festo – P.BE-CPX-CTEL-EN – 1601b – English...
1) These parameters are read out only during initialisation of the CTEL master module. Subsequent changes of the parameters have no effects. Bits 0 ... 3 cannot be written in combination with the Festo Maintenance Tool and the operator unit. They are represen...
1) These parameters are read out only during initialisation of the CTEL master module. Subsequent changes of the parameters have no effects. Bits 0 ... 3 cannot be written in combination with the Festo Maintenance Tool and the operator unit. They are represen...
Page 34
The I-Port is deactivated and cannot be used. A device that is still connected results in output of an “I-Port configuration error”. The set address space is also assigned for deactivated I-Ports in the CPX system. Festo – P.BE-CPX-CTEL-EN – 1601b – English...
For each connected device, 8 bytes are available for representation of the device parameters. These parameters are individually interpreted by each device and are defined in the description of the corres ponding device. Festo – P.BE-CPX-CTEL-EN – 1601b – English...
Observe the notes on “Force”, “Idle mode” and “Fail safe” in the CPX system description and in the description for the operator unit if the CPX bus node used supports these parameterisation types. Festo – P.BE-CPX-CTEL-EN – 1601b – English...
The “Force” function can also be called up via the “Monitoring/Forcing (M)” menu. This function allows you to force signal statuses during the commissioning phase for test purposes. The representation of the I-Port devices also applies accordingly to the “Idle mode” and “Fail safe” functions. Festo – P.BE-CPX-CTEL-EN – 1601b – English...
Commissioning Commissioning with the Festo Maintenance Tool software (CPX-FMT) The Festo Maintenance Tool software (CPX-FMT) can also be used for commissioning, parameterisation and advanced diagnostics of the CTEL master module. The current soft ware version can be found online (è www.festo.com/sp).
Advantage: Fast “on-site” error detection; (FMT) diagnostics also possible from a higher automation level Tab. 5.1 Diagnostics options The available diagnostic information may depend on the settings of the CPX bus node or on the parameterisation. Festo – P.BE-CPX-CTEL-EN – 1601b – English...
Within a CPX terminal, diagnostic/error messages with reference to inputs have priority over diagnostic/error messages of outputs. This principle of error prioritisation also finds use in the CTEL master module in the I/O mixed operation. Festo – P.BE-CPX-CTEL-EN – 1601b – English...
CPX system start with setting “Stored parameter” at the start of the CPX parameters” terminal Process variable range underflow Process data inconsistent, check Process variable range overflow Process data inconsistent, check Festo – P.BE-CPX-CTEL-EN – 1601b – English...
LED indicators for diagnostics of the CPX terminal are available on the I-Port devices and on the CTEL master module (è 2.3 Display components). The significance of the LEDs on the I-Port devices can be found in the description of the respective device. Festo – P.BE-CPX-CTEL-EN – 1601b – English...
I-Port devices. The I-Port devices connected to a CTEL master module are treated as input or output channels within the CPX terminal. Detailed information about the I/O diagnostic interface and diagnostic memory can be found in the CPX system description (è P.BE-CPX-SYS-…). Festo – P.BE-CPX-CTEL-EN – 1601b – English...
Module data (MD) … “Diagnostics” menu Fig. 5.1 General information regarding operation and commissioning of the CPX terminal using the operator unit can be found in the description for the operator unit (è P.BE-CPX-MMI-1-…). Festo – P.BE-CPX-CTEL-EN – 1601b – English...
Diagnostics and error handling Diagnostics with the Festo Maintenance Tool (CPX-FMT) The Festo Maintenance Tool (CPX-FMT) offers extended functions for diagnostics and troubleshooting with the CTEL master module. Fig. 5.2 General information regarding operation and commissioning of the CPX terminal with the FMT can be found in the CPX system description (è...
PS or PL, the I-Port involved is always switched off completely (PS and PL off ). Behaviour after elimination of the error can be set via the parameter “Behaviour after I-Port short cir cuit” (è 4.6.4 Parameter “Behaviour after I-Port short circuit”). Festo – P.BE-CPX-CTEL-EN – 1601b – English...
H-rail mounting Continuous shock resist Wall mounting ance H-rail mounting 1) Connected devices may only satisfy a lower degree of protection or a smaller temperature range, etc. 2) SG = severity level Tab. A.1 Festo – P.BE-CPX-CTEL-EN – 1601b – English...
Page 51
U Yes, with potential-isolated supply EL/SEN and load voltage supply U Supply PS/PL between the I-Ports Functional earth connection Optional, through earthing plate Mains buffering time [ms] Tab. A.2 Festo – P.BE-CPX-CTEL-EN – 1601b – English...
Totality of the combined CPX modules, including a bus node, without pneu matics. Device Any module that can be connected to the CTEL master module via the I-port interface. Festo Maintenance Tool. PC software for commissioning, configuration and extended diagnostics of CPX terminals. Digital input I-module Input module I/O length Number of bytes available for inputs and outputs.
....... . . – with the Festo Maintenance Tool (FMT) .
Page 57
– Determine current consumption ..– Error at the PL/PS supply ....Festo – P.BE-CPX-CTEL-EN – 1601b – English...
Page 59
Copyright: Festo SE & Co. KG Postfach 73726 Esslingen Germany Phone: +49 711 347-0 Fax: +49 711 347-2144 E-mail: service_international@festo.com Reproduction, distribution or sale of this document or communica tion of its contents to others without express authorization is Internet: prohibited.