Mitsubishi Melsec-Q Series User Manual page 81

Hide thumbs Also See for Melsec-Q Series:
Table of Contents

Advertisement

Item
Program memory
Memory card (RAM)
Max.
Flash
Memory
number of
card
card
files stored
(ROM)
ATA card
Standard RAM
Standard ROM
No. of times of writing data into the
program memory
No. of times of writing data into the
standard ROM
No. of I/O device points
(No. of points usable on program.)
No. of I/O points
(No. of points accessible to the
actual I/O module.)
*6
Internal relay [M]
*6
Latch relay [L]
*6
Link relay [B]
*6
Timer [T]
*6
Retentive timer [ST]
*6
Counter [C]
*6
Data register [D]
Extended data register [D]
*6
Link register [W]
Extended link register [W]
*6
Annunciator [F]
*6
Edge relay [V]
*6
Link special relay [SB]
*6
Link special register [SW]
*4: The one write operation may not be counted as one writing to a program memory.
The number of writing to the program memory can be checked by the special register (SD682 and SD683).
*5: The one write operation may not be counted as one writing to the standard ROM.
The number of writing to the standard ROM can be checked by the special register (SD687 and SD688).
*6: The number of points can be changed within the setting range. (
Fundamentals))
CHAPTER4 HARDWARE SPECIFICATIONS OF THE CPU MODULE
Table4.5 Performance specifications
Q00UJCPU
Q00UCPU
32
----
----
----
----
256 points
(X/Y0 to FF)
8192 points by default (M0-8191) (changeable)
8192 points by default (L0-8191) (changeable)
8192 points by default (B0 to 1FFF) (changeable)
2048 points by default (T0 to 2047) (changeable)
(Sharing of low- and high-speed timers)
The low- and high-speed timers are specified by the instructions.
The measurement unit of the low- and high-speed timers is set up by parameters.
(Low-speed timer: 1 to 1000ms, 1ms unit, 100ms by default)
(High-speed timer: 0.1 to 100.0ms, 0.1ms unit, 10.0ms by default)
0 point by default (sharing of the low- and high-speed retentive timers) (changeable)
The low- and high-speed retentive timers are specified by the instructions.
The measurement unit of the low- and high-speed retentive timers is set up by parameters.
(Low-speed retentive timer: 1 to 1000ms, 1ms unit, 100ms by default)
(High-speed retentive timer: 0.1 to 100.0ms, 0.1ms unit, 10.0ms by default)
• Normal counter, 1024 points by default (C0 to 1023) (changeable)
12288 points by default (D0 to 12287) (changeable)
----
8192 points by default (W0 to 1FFF) (changeable)
----
2048 points by default (F0 to 2047) (changeable)
2048 points by default (V0 to 2047) (changeable)
2048 points by default (SB0 to 7FF) (changeable)
2048 points by default (SW0 to 7FF) (changeable)
Universal model QCPU
Q01UCPU
Q02UCPU
319 (When the Q3MEM-8MBS is
128
*4
Max. 100000 times
*5
Max. 100000 times
8192 points (X/Y0 to 1FFF)
1024 points
2048 points
(X/Y0 to 3FF)
(X/Y0 to 7FF)
0 points by default (changeable)
0 points by default (changeable)
QnUCPU User's Manual (Function Explanation, Program
Q03UDCPU
Q03UDECPU
64
124
used)
288
511
256
4096 points (X/Y0
to FFF)
4 - 17
1
2
3
4
5
6
7
8

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents