Mitsubishi Melsec-Q Series User Manual page 376

Hide thumbs Also See for Melsec-Q Series:
Table of Contents

Advertisement

Error
Code
Error Contents and Cause
(SD0)
[SP.UNIT LAY ERR.]
• Two or more MELSECNET/H modules are
mounted.
• Two or more CC-Link IE controller network mod-
ules are mounted.
• Two or more Ethernet modules are mounted.
■Collateral information
• Common Information:Module No.
• Individual Information:–
■Diagnostic Timing
• At power ON/At reset
[SP.UNIT LAY ERR.]
• Five or more MELSECNET/H and CC-Link IE
controller network modules in total are mounted
in the entire system.
• Two or more MELSECNET/H modules are
mounted in the entire system.
• Two or more CC-Link IE controller network mod-
ules are mounted in the entire system.
• Two or more Ethernet modules are mounted in
the entire system.
■Collateral information
• Common Information:Module No.
• Individual Information:–
■Diagnostic Timing
• At power ON/At reset
[SP.UNIT LAY ERR.]
• Three or more MELSECNET/H and CC-Link IE
controller network modules in total are mounted
in the entire system.
• Three or more Ethernet interface modules are
mounted in the entire system.
2106
■Collateral information
• Common Information:Module No.
• Individual Information:–
■Diagnostic Timing
• At power ON/At reset
[SP.UNIT LAY ERR.]
• Five or more MELSECNET/H and CC-Link IE
controller network modules in total are mounted
in the entire system.
• Five or more Ethernet interface modules are
mounted in the entire system.
■Collateral information
• Common Information:Module No.
• Individual Information:–
■Diagnostic Timing
• At power ON/At reset
[SP.UNIT LAY ERR.]
• Three or more CC-Link IE controller network
modules are mounted in the entire system.
• Five or more MELSECNET/H and CC-Link IE
controller network modules in total are mounted
in the entire system.
■Collateral information
• Common Information:Module No.
• Individual Information:–
■Diagnostic Timing
• At power ON/At reset
*6
The module whose first 5 digits of serial No. is "09012" or later.
*7
The Universal model QCPU except the Q00UJCPU, Q00UCPU, Q01UCPU, and Q02UCPU.
*9
The module whose first 5 digits of serial No. is "10042" or later.
12 - 81
Corrective Action
• Reduce the number of MELSECNET/H modules
to one.
• Reduce the number of CC-Link IE controller net-
work modules to one.
• Reduce the number of Ethernet modules to one.
• Reduce the number of MELSECNET/H and CC-
Link IE controller network modules to four or less
in total in the entire system.
• Reduce the number of MELSECNET/H modules
to one in the entire system.
• Reduce the number of CC-Link IE controller net-
work modules to one in the entire system.
• Reduce the number of Ethernet modules to one
in the entire system.
• Reduce the MELSECNET/H and CC-Link IE con-
troller network modules up to two or less in the
entire system.
• Reduce the Ethernet interface modules up to two
or less in the entire system.
• Reduce the MELSECNET/H and CC-Link IE con-
troller network modules up to four or less in the
entire system.
• Reduce the Ethernet interface modules up to four
or less in the entire system.
• Reduce the CC-Link IE controller network mod-
ules up to two or less in the entire system.
• Reduce the total number of the MELSECNET/H
and CC-Link IE controller network modules up to
four or less in the entire system.
LED Status
Corresponding
CPU Status
CPU
Q00UJ
Q00U/Q01U
RUN:
Off
ERR.:
Q02U
Flicker
CPU Status:
Stop
*7
QnU
*6
Qn(H)
*9
QnPH
QnPRH
*9

Hide quick links:

Advertisement