Advertisement

(4) Positioning module, channel-isolated pulse input module
Use shielded cables for the external wiring, and ground the shields of the external wiring cables to the control box
with the AD75CK cable clamp (Mitsubishi).
(Ground the shields 20 to 30cm away from the module.)
The AD75CK allows up to four cables to be grounded if the outside diameter of the shielded cable is about 7mm.
(5) Temperature control module
Use shielded cables for the external wiring, and ground the shields of the external wiring cables to the control box
with the AD75CK cable clamp (Mitsubishi).
(Ground the shields 20 to 30cm away from the module.)
The AD75CK allows up to four cables to be grounded if the outside diameter of the shielded cable is about 7mm.
The required number of AD75CKs is indicated in Table9.2. (When cables of 7mm outside diameter are used for
all wiring.)
9 - 6
Inside control box
20 to 30cm
(7.87 to 11.81 inch)
AD75CK
Figure 9.8 AD75CK cable clamp mounting position
Inside control box
20 to 30cm
(7.87 to 11.81 inch)
AD75CK
Figure 9.9 AD75CK cable clamp mounting position