Error
Code
Error Contents and Cause
(SD0)
[SP. UNIT ERROR]
An instruction, which on execution specifies other
stations, has been used for specifying the host
CPU. (An instruction that does not allow the host
CPU to be specified).
2114
■Collateral information
• Common Information:Module No. (Slot No.)
• Individual Information:Program error location
■Diagnostic Timing
• When instruction executed/ STOP
[SP. UNIT ERROR]
An instruction, which on execution specifies the
host CPU, has been used for specifying other
CPUs. (An instruction that does not allow other sta-
tions to be specified).
2115
■Collateral information
• Common Information:Module No. (Slot No.)
• Individual Information:Program error location
■Diagnostic Timing
• When instruction executed/ STOP
[SP. UNIT ERROR]
• An instruction that does not allow the under the
control of another CPU to be specified is being
used for a similar task.
• Instruction was executed for the A or QnA mod-
ule under control of another CPU.
2116
■Collateral information
• Common Information:Module No. (Slot No.)
• Individual Information:Program error location
■Diagnostic Timing
• When instruction executed/ STOP
[SP. UNIT ERROR]
A CPU module that cannot be specified in the
instruction dedicated to the multiple CPU system
was specified.
■Collateral information
2117
• Common Information:Module No. (Slot No.)
• Individual Information:Program error location
■Diagnostic Timing
• When instruction executed/ STOP
[SP. UNIT ERROR]
When the online module change setting is set to be
"enabled" in the PLC parameter in a multiple CPU
system, intelligent function module controlled by
other CPU using the FROM instruction/intelligent
2118
function module device (U \ G) is specified.
■Collateral information
• Common Information:Module No. (Slot No.)
• Individual Information:Program error location
■Diagnostic Timing
• When instruction executed
*3
The function version is B or later.
*7
The Universal model QCPU except the Q00UJCPU, Q00UCPU, Q01UCPU, and Q02UCPU.
Corrective Action
RUN
Read the individual information of the error using
RUN
the GX Developer, check the program correspond-
ing that value (program error location), and make
correction.
RUN
RUN
• When performing the online module change in a
multiple CPU system, correct the program so that
access will not be made to the intelligent function
module controlled by the other CPU.
• When accessing the intelligent function module
controlled by the other CPU in a multiple CPU
system, set the online module change setting to
be "disabled" by parameter.
CHAPTER12 TROUBLESHOOTING
LED Status
Corresponding
CPU Status
CPU
Q00J/Q00/Q01
*3
Qn(H)
QnPH
QnU
Q00J/Q00/Q01
*3
Qn(H)
QnPH
RUN:
Off/On
ERR.:
Flicker/On
CPU Status:
Q00J/Q00/
Stop/Continue
*3
Q01
*3
Qn(H)
QnPH
QnU
*3
Qn(H)
QnPH
*7
QnU
12 - 84
*3
12
*3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents