Mitsubishi Melsec-Q Series User Manual page 461

Hide thumbs Also See for Melsec-Q Series:
Table of Contents

Advertisement

Error code
Error item
(Hexadecimal)
4A00
H
Link-related
error
4A01
H
4A02
H
4A03
H
4B00
H
4B01
H
Target-related
error
4B02
H
4B03
H
4B04
H
4C00
H
Multiple CPU-
4C08
H
related error
4C09
H
Table12.2 Error code
Error details
• Access to the specified station cannot be
made since the routing parameters are not
set to the start source CPU module and/or
relay CPU module.
• For routing via a multiple CPU system, the
control CPU of the network module for data
routing has not started.
• When System A/System B is not yet identi-
fied in a redundant system configuration,
communication was made with the other
station via the network module.
The network of the No. set to the routing parame-
ters does not exist.
Access to the specified station cannot be made.
A request for network test was issued.
An error occurred in the access destination or
relay station, or the specified transfer setup
(request destination module I/O number) is illegal.
The target is not the No. 1 CPU of the multiple
CPU system.
The request is not addressed to the CPU module.
• The specified route is not supported by the
specified CPU module version.
• The communication target CsPU is not
mounted.
The specified transfer setup (request destination
module I/O number) is not supported.
The specified device is unavailable for the motion
CPU or outside the device range.
There are a total of 33 or more DDWR and DDRD
requests.
The specification of the requested CPU module
No. is illegal.
CHAPTER12 TROUBLESHOOTING
Corrective action
• Set to the related stations the routing parameters for
access to the specified station.
• Retry after a while, or start communication after con-
firming that the system for data routing has started.
• In a redundant system configuration, connect the
tracking cable, start System A/System B normally, and
then restart communication.
Check and correct the routing parameters set to the related
stations.
• Check the network module/link module for an error or
offline status.
• Check to see if the network number/PC number setting
has no mistake.
Check the request data of the MC protocol, etc.
• Take corrective action after checking the error that
occurred at the specified access destination or the
relay station to the accessed station.
• Check the transfer setup (request destination module
I/O number or programmable controller number) in the
request data of the MC protocol, etc.
Execute the request for the No. 1 CPU of the multiple CPU
system.
Perform operation for the module that can execute the speci-
fied function.
Check whether the specified route is supported or not.
In the target setup, an illegal value is set as the head I/O
number of the target module.
Check the request data contents.
Execute again after reducing the number of DDWR and
DDRD requests to be executed simultaneously.
Check the request data contents.
12
12 - 166

Hide quick links: