Table12.10 Output circuit troubleshooting (Continued)
Situation
Erroneous output due to the stray capacitance (C) between
collector and emitter of hotocoupler.
There is no erroneous output at normal load.
An erroneous output may occur at high sensitivity load
(such as solid state relay).
Output module, Combined module
Photocoupler
C
When the
external power
supply turns
on, the load is
turned on for a
moment.
I
Cause
Tr1
IC
Y0
12/24VDC
Constant
COM
voltage circuit
CHAPTER12 TROUBLESHOOTING
Countermeasure
When turning on or off the external
power, check that the external power
supply rising edge is 10ms or more, and
switch the SW1 to the primary side of
external power supply.
Primary
side
external power supply
SW1
When switching to the secondary side of
the external power supply is required, the
external power supply rising edge
connected a condenser must be slow,
and measured 10ms or more.
Sink output
Y0
0V
SW
COM
24V
Source output
Y0
0V
COM
*: Measures will not be effective to the
following module due to the characterictic
of external power supply circuit.
• QY81P
Secondary
side
Programmable
controller
R1
SW
C1
24V
R1
SW
C1
24V
12 - 184
1
2
3
12
5
6
7
8