Error code
Error item
(Hexadecimal)
4021
H
4022
H
4023
H
4024
H
4025
H
4026
H
CPU file related
4027
H
error
4028
H
4029
H
402A
H
402B
H
402C
H
4030
H
4031
H
4032
H
CPU device
specified error
4033
H
4034
H
12 - 147
Table12.2 Error code
Error details
The specified drive memory does not exist or
there is an error.
The file with the specified file name or file No.
does not exist.
The file name and file No. of the specified file do
not match.
The specified file cannot be handled by a user.
The specified file is processing the request from
the other peripheral device.
The file password or drive keyword set to the tar-
get drive (memory) must be specified.
The specified range exceeds the file range.
The same file already exists.
The specified file capacity cannot be obtained.
The specified file is abnormal.
The request contents cannot be executed in the
specified drive memory.
The requested operation cannot be executed cur-
rently.
The specified device name cannot be handled.
The specified device No. is outside the range.
There is a mistake in the specified device qualifi-
cation.
The unusable device name
(TS,TC,SS,SC,CS,CC) must be specified in MC
protocol random reading, random writing (word),
monitor registeration and monitor command.
Writing cannot be done because the specified
device is for system use.
Cannot be executed since the completion device
for the dedicated instruction cannot be turned
ON.
Corrective action
• Check the specified drive memory status.
• After backing up the data in the CPU module, execute
programmable controller memory format.
Check the specified file name and file No.
Delete the file and then recreate the file.
Do not access the specified file.
Forcibly execute the request, or make the request again after
the processing from the other peripheral device is com-
pleted.
Make access after specifying the file password or drive key-
word set to the target drive (memory).
Check the specified range and access within that range.
Forcefully execute the request forcibly.
Or reexecute after changing the file name.
Revise the specified file contents.
Or reexecute after cleaning up and reorganizing the speci-
fied drive memory.
After backing up the data in the CPU module, execute pro-
grammable controller memory format.
Execute again after setting the CPU module to the STOP
status.
Execute programmable controller memory arrangement to
increase the continuous free space of the drive (memory).
Execute again after a while.
Check the specified device name.
• Check the specified device No.
• Check the device assignment parameters of the CPU
module.
• Check the specified device qualification method.
• Check the specified device name.
Do not write the data in the specified device, and do not turn
on or off.
Since the completion device for the target station CPU mod-
ule cannot be turned ON by the SREAD instruction/SWRITE
instruction, execute again after setting the operating status of
the target station CPU module to the RUN status.