Mitsubishi Melsec-Q Series User Manual page 392

Hide thumbs Also See for Melsec-Q Series:
Table of Contents

Advertisement

Error
Code
Error Contents and Cause
(SD0)
[PARAMETER ERROR]
The automatic refresh range of the multiple CPU
system exceeded the file register capacity.
■Collateral information
• Common Information:File name/ Drive name
• Individual Information:Parameter number
■Diagnostic Timing
• When an END instruction executed
[PARAMETER ERROR]
3003
The number of devices set at the PLC parameter
device settings exceeds the possible CPU module
range.
■Collateral information
• Common Information:File name/ Drive name
• Individual Information:Parameter number
■Diagnostic Timing
• At power-On/ At reset/ STOP
At writing to progurammable controller
[PARAMETER ERROR]
The parameter file is incorrect.
Alternatively, the contents of the file are not param-
eters.
■Collateral information
3004
• Common Information:File name/ Drive name
• Individual Information:Parameter number
■Diagnostic Timing
• At power-On/ At reset/ STOP
At writing to progurammable controller
[PARAMETER ERROR]
The contents of the parameter are broken.
■Collateral information
• Common Information:File name/ Drive name
3005
• Individual Information:Parameter number
■Diagnostic Timing
• At power-ON/ At reset/ STOP
[PARAMETER ERROR]
• The high speed interrupt is set in a Q02CPU.
• The high speed interrupt is set in a multiple CPU
system.
• The high speed interrupt is set when aQA1S6 B
or QA6 B is used.
• No module is installed at the I/O address desig-
3006
nated by the high speed interrupt.
■Collateral information
• Common Information:File name/ Drive name
• Individual Information:Parameter number
■Diagnostic Timing
• At power-On/ At reset/ STOP
At writing to progurammable controller
*1
The function version is B or later.
*4
The module whose first 5 digits of serial No. is "04012" or later.
*7
The module whose first 5 digits of serial No. is "09012" or later.
*9
The module whose first 5 digits of serial No. is "10042" or later.
*10
The Universal model QCPU except the Q00UJCPU.
12 - 97
Change the file register file for the one refresh-
enabled in the whole range.
• Read the individual information of the error using
the peripheral device, check the parameter item
corresponding to the numerical value (parameter
No.), and correct it.
• If the error is still generated following the correc-
tion of the parameter settings, the possible cause
is the memory errorm of the CPU module's pro-
gram memory or the memory card. (Contact your
RUN/
local Mitsubishi representative.)
Check whether the parameter file version
is
.QPA, and check the file contents to be
sure they are parameters.
RUN/
• Read the individual information of the error using
the peripheral device, check the parameter item
corresponding to the numerical value (parameter
No.), and correct it.
• Write the modified parameter items to the CPU
module again, and power-on the Programmable
Controller or reset the CPU module.
• When the same error occurs again, the hardware
RUN
is faulty. Contact your local Mitsubishi represen-
tative, explaining a detailed description of the
problem.
• Delete the setting of the Q02CPU' s high speed
interrupt. To use high speed interrupts, change
the CPU module to one of the Q02H/Q06H/
Q12H/Q25HCPU.
• To use a multiple CPU system, delete the setting
of the high-speed interrupt. To use high speed
interrupts, change the system to a single CPU
system.
• To use either the QA1S6 B or QA6 B, delete
the setting of the high speed interrupt. To use
high speed interrupts, do not use the QA1S6 B/
QA6 B.
RUN/
• Re-examine the I/O address designated by the
high speed interrupt setting.
Corrective Action
LED Status
Corresponding
CPU Status
CPU
*1
Qn(H)
QnPH
*10
QnU
QCPU
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
*7
Qn(H)
*9
QnPH
QnPRH
*4
Qn(H)
*9