12.2.36 When clock data cannot be set by SNTP
Refer to the following flowchart when clock data cannot be set by SNTP.
Time cannot be set by SNTP.
Is the time setting
functioning? (See Ethernet
diagnosis screen or SD1270.)
YES
Failed to set time?
(See Ethernet diagnosis screen or
SD1270.)
NO
Is the multiple CPU function used?
NO
Are the prameters of
the Built-in Ethernet port QCPU
correct? *
YES
Check if time was overwritten from the
sequence program or another device.
12 - 57
NO
Check the time setting function settings. *
NO
Is the time setting available?
YES
YES
Has time been set on CPU
No.1 in the multiple CPU system?
YES
NO
Enter correct parameters.
1
NO
Is the time setting available?
YES
(To the next page)
NO
Set time on CPU No.1.
NO
Is the time setting available?
YES
1
YES
Completed