Mitsubishi Melsec-Q Series User Manual page 154

Hide thumbs Also See for Melsec-Q Series:
Table of Contents

Advertisement

No.
Name
9)
Terminal cover
10)
Module fixing screw hole
11)
Module mounting lever
*1: Although the POWER LED turns on in red for a moment immediately after the power supply is turned on or off, redundant power supply
modules is not faulty.
Q64RP automatically switches the input range 100/200VAC.
Therefore, it is not compatible with the intermediate voltage (133 to 169VAC).
The CPU module may not work normally if the above intermediate voltage is applied.
Supply power to redundant power supply modules from separate power sources (a redundant power supply system).
Ground the LG and FG terminals to the protective ground conductor.
5 - 35
Protective cover of the terminal block
Screw hole for securing a module to the base unit.
M3 12 screw (user-prepared) (Tightening torque : 0.36 to 0.48N•m)
Used to mount a module on the base unit.