Mitsubishi Melsec-Q Series User Manual page 132

Hide thumbs Also See for Melsec-Q Series:
Table of Contents

Advertisement

Item
Mounting position
Applicable base unit
*10
Input power supply
Input frequency
Input voltage distortion
factor
Max. input apparent
power
Max. input power
Inrush current
5VDC
Rated output
current
24VDC
External output voltage
Overcurrent
5VDC
*1
protection
24VDC
5VDC
Overvoltage
*2
protection
24VDC
Efficiency
Allowable momentary
*3
power failure period
Dielectric withstand
voltage
Insulation resistance
• By noise simulator of 1500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency
Noise durability
• Noise voltage IEC 61000-4-4, 2KV
Operation indication
Fuse
Application
Rated switching
voltage, current
Minimum
switching load
Response time
Life
Surge suppres-
sor
Fuse
*10: When using the Q61P-D in the system configured with a A/AnS series module, the power supply modules mounted on the main base
unit and extension base unit must be turned on and off simultaneously.
5 - 13
Table5.8 Power supply module specifications
Performance Specifications
Power supply module mounting slot
Q3
Within 5% (
Between input -LG batched and output-FG batched
2830VAC rms/3 cycles (2000m (6562 feet))
Input and LG batched, output and FG batched, batch input - LG, batch output - FG
10M
or higher by 500VDC insulation resistance tester
LED indication (POWER LED, LIFE LED)
Built-in (User-unchangeable)
,
ERR. contact
LIFE OUT contact (
OFF to ON: 10ms max. ON to OFF: 12ms max.
Mechanical : More than 20 million times
Electrical : More than 100 thousand times at rated switching voltage, current
Q61P-D
B, Q3
DB, Q6
B
+10%
100 to 240VAC
-15%
(85 to 264VAC)
50/60Hz
5%
Section 5.2.4)
130VA
----
*5
20A within 8ms
6A
----
----
6.6A or more
----
5.5 to 6.5V
----
70% or more
Within 20ms
Section 5.3)
24VDC, 0.5A
5VDC, 1mA
No
No