Error Contents and Cause
Code
1107
[RAM ERROR]
The work area RAM in the CPU module is faulty.
■Collateral information
• Common Information:–
1108
• Individual Information:–
■Diagnostic Timing
• At power ON/ At reset
[RAM ERROR]
The work area RAM in the CPU module is faulty.
■Collateral information
• Common Information:–
1109
• Individual Information:–
■Diagnostic Timing
• Always
[TRK. CIR. ERROR]
A fault was detected by the initial check of the
tracking hardware.
■Collateral information
1110
• Common Information:–
• Individual Information:–
■Diagnostic Timing
• At power ON/ At reset
[TRK. CIR. ERROR]
A tracking hardware fault was detected.
■Collateral information
• Common Information:–
1111
• Individual Information:–
■Diagnostic Timing
• At power ON/ At reset
1112
[TRK. CIR. ERROR]
A tracking hardware fault was detected during run-
ning.
• The tracking cable was disconnected and rein-
serted without the standby system being pow-
ered off or reset.
• The tracking cable is not secured by the connec-
tor fixing screws.
1113
• The error occurred at a startup since the redun-
dant system startup procedure was not followed.
■Collateral information
• Common Information:–
• Individual Information:–
■Diagnostic Timing
• During running
[TRK. CIR. ERROR]
A fault was detected by the initial check of the
tracking hardware.
■Collateral information
1115
• Common Information:–
• Individual Information:–
■Diagnostic Timing
• At power ON/ At reset
*8
The module whose first 5 digits of serial No. is "08032" or later.
*9
The module whose first 5 digits of serial No. is "09012" or later.
Corrective Action
This suggests a CPU module hardware fault. (Con-
tact your local Mitsubishi representative.)
• Start after checking that the tracking cable is con-
nected.
If the same error is displayed again, the cause is
the hardware fault of the tracking cable or CPU
module. (Please contact your local Mitsubishi
representative, explaining a detailed description
of the problem.)
• Confirm the redundant system startup procedure,
and execute a startup again. For details, refer to
the QnPRHCPU User's Manual (Redundant Sys-
tem).
This suggests a CPU module hardware fault. (Con-
tact your nearest Mitsubishi representative.)
CHAPTER12 TROUBLESHOOTING
LED Status
Corresponding
CPU Status
CPU
QnPRH
*8
Qn(H)
*8
QnPH
*9
QnPRH
QnPRH
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop