Error
Error Contents and Cause
Code
[SP. UNIT DOWN]
• There was no response from the intelligent func-
tion module/special function module in the initial
processing.
• The size of the buffer memory of the intelligent
function module/special function module is
invalid.
1401
• The unsupported module is mounted.
■Collateral information
• Common Information:Module No.(Slot No.)
• Individual Information:–
■Diagnostic Timing
• At power ON/ At reset/When intelligent function
module is accessed
[SP. UNIT DOWN]
The intelligent function module/special function
module was accessed in the program, but there
was no response.
■Collateral information
1402
• Common Information:Module No. (Slot No.)
• Individual Information:Program error location
■Diagnostic Timing
• When an intelligent function module access
instruction is executed
[SP. UNIT DOWN]
• The unsupported module is mounted.
■Collateral information
• Common Information:Module No. (Slot No.)
• Individual Information:–
■Diagnostic Timing
• When an END instruction executed
[SP. UNIT DOWN]
• There was no response from the intelligent func-
tion module/special function module when the
1403
END instruction is executed.
• An error is detected at the intelligent function
module/special function module.
• The I/O module (intelligent function module/spe-
cial function module) is nearly removed, com-
pletely removed, or mounted during running.
■Collateral information
• Common Information:Module No. (Slot No.)
• Individual Information:–
■Diagnostic Timing
• Always
[CONTROL-BUS. ERR.]
When performing a parameter I/O allocation the
intelligent function module/special function module
could not be accessed during initial communica-
tions.
(On error occurring, the head I/O number of the
corresponding intelligent function module/special
1411
function module is stored in the common informa-
tion.)
■Collateral information
• Common Information:Module No. (Slot No.)
• Individual Information:–
■Diagnostic Timing
• At power ON/ At reset
*2
In the QCPU, either error stop or continue can be selected for each intelligent function module by the parameters.
Corrective Action
When the unsupported module is mounted, remove
it.
When the corresponding module is supported, this
suggests the intelligent function module/special
function module, CPU module and/or base unit is
expecting a hardware fault (Contact your local Mit-
subishi representative.)
This suggests the intelligient function module/spe-
cial function module , CPU module and/or base unit
is expecting a hardware fault (Contact your local
Mitsubishi representative.)
When the unsupported module is mounted, remove
it.
When the corresponding module is supported, this
suggests the intelligent function module/special
function module , CPU module and/or base unit is
expecting a hardware fault (Contact your local Mit-
subishi representative.)
The CPU module, base module and/or the intelli-
gent function module/special function module that
was accessed is experiencing a hardware fault.
(Contact your local Mitsubishi representative.)
Reset the CPU module and RUN it again. If the
same error is displayed again, the intelligent func-
tion module/special function module, CPU module
or base unit is faulty. (Contact your local Mitsubishi
representative.)
CHAPTER12 TROUBLESHOOTING
LED Status
Corresponding
CPU Status
CPU
RUN:
Off/On
ERR.:
Flicker/On
QCPU
CPU Status:
Stop/
*2
Continue
RUN:
Off
ERR.:
Flicker
QCPU
CPU Status:
Stop
12 - 72