4 - 6
Error! Reference source not found. Error! Reference source not found.
Step 10: When the PLC fault screen appears (seen below) press the F3 key (ENTER).
Step 11: Press F3 (ENTER) on the first screen that displays to Restore PLC Program from Memory Card to PLC.
Step 12: The PLC program will now be saved from the memory card to the PLC. This may take several minutes.
Step 13: Press F4 (OK).
Step 14: Turn off power to bar feeder.
Step 15: Move the RUN/STOP switch to RUN position.
Step 16: Restore power to the bar feeder.
Procedure complete.
QUICK LOAD SERVO S3

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the QUICK LOAD SERVO S3 and is the answer not in the manual?

Questions and answers

tom,
March 18, 2025

LNS BARFEEDER sps no response , how do i fix this error

1 comments:
Mr. Anderson
March 18, 2025

The SPS No Response alarm on the QUICK LOAD SERVO S3 occurs due to a communication problem between the remote control station and the LNS PLC. To fix this error:

1. Check the connectors between the PLC and the remote control station inside the cross piece to ensure they are correctly attached.
2. Verify continuity between the PLC and the remote control station.

These steps help restore proper communication and resolve the error.