Chapter 1: Alarms
A
n error has occurred during setup or cycling of the bar feeder. When an error occurs, an alarm message is generated on
the remote control station.
troubleshooting guide discusses every alarm that the bar feed may generate. In conjunction with each alarm will be a
brief description of what the alarm is and a few tips and procedures of how to correct the problem.
Chapter 1:
Also provided are some possible causes as to why the error has occurred.
Figure 1-1 Remote control station

Alarms

QUICK LOAD SERVO S3
1 - 1
This

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the QUICK LOAD SERVO S3 and is the answer not in the manual?

Questions and answers

tom,
March 18, 2025

LNS BARFEEDER sps no response , how do i fix this error

1 comments:
Mr. Anderson
March 18, 2025

The SPS No Response alarm on the QUICK LOAD SERVO S3 occurs due to a communication problem between the remote control station and the LNS PLC. To fix this error:

1. Check the connectors between the PLC and the remote control station inside the cross piece to ensure they are correctly attached.
2. Verify continuity between the PLC and the remote control station.

These steps help restore proper communication and resolve the error.