Determining Display Firmware - LNS QUICK LOAD SERVO S3 Troubleshooting And Spare Parts Manual

Hide thumbs Also See for QUICK LOAD SERVO S3:
Table of Contents

Advertisement

Error! Reference source not found. Error! Reference source not found.
4 - 3

Determining Display Firmware

To ensure that the right procedure is used to perform a Software Update or to restore software, check the
display on the bar feed to determine its firmware version: 1.17a or 2.08.
In order to check the version of the firmware, turn the main bar feed power off and then back on again.
During the power up, the first screen will show the firmware version of the display.
Firmware v 1.17a
Firmware v 2.08
Firmware v 2.08
(No card is present or the card is blank)
If the display has firmware version 1.17a, proceed to page 4-3. If the display has firmware version 2.08,
proceed to page 4-20.
QUICK LOAD SERVO S3

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the QUICK LOAD SERVO S3 and is the answer not in the manual?

Questions and answers

tom,
March 18, 2025

LNS BARFEEDER sps no response , how do i fix this error

1 comments:
Mr. Anderson
March 18, 2025

The SPS No Response alarm on the QUICK LOAD SERVO S3 occurs due to a communication problem between the remote control station and the LNS PLC. To fix this error:

1. Check the connectors between the PLC and the remote control station inside the cross piece to ensure they are correctly attached.
2. Verify continuity between the PLC and the remote control station.

These steps help restore proper communication and resolve the error.

This answer is automatically generated

Table of Contents

Save PDF