Chapter 1: Alarms
A007 – Main Access Cover Open
MAIN ACCESS COVER
OPEN!
CLOSE MAIN COVER TO
RESUME OPERATIONS
Description:
The Main Access Cover Open alarm occurs whenever the PLC detects input (I0.2 – SQ10). The problem is generated, as a safety
precaution, when the main access cover is opened to prevent any movement in the bar feeder if the operator or service technician
needs to perform any work inside the unit.
Solution:
Press the HELP key on the remote control station. Press the F4 key (Page Down icon) twice.
Case
Input
Remote Pendant
1
Bit 2 = 1
2
Bit 2 = 0
For case 2, after the solutions have been completed, press the STOP key on the remote control station to clear the message and
reset the alarm.
A007
MODULE 0
76543210
Close the main access cover.
100
MODULE 0
Alarm needs to be cleared. Press the STOP key on the
76543210
remote control station to clear the message and reset
the alarm.
0
Solution
QUICK LOAD SERVO S3
1 - 7

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the QUICK LOAD SERVO S3 and is the answer not in the manual?

Questions and answers

tom,
March 18, 2025

LNS BARFEEDER sps no response , how do i fix this error

1 comments:
Mr. Anderson
March 18, 2025

The SPS No Response alarm on the QUICK LOAD SERVO S3 occurs due to a communication problem between the remote control station and the LNS PLC. To fix this error:

1. Check the connectors between the PLC and the remote control station inside the cross piece to ensure they are correctly attached.
2. Verify continuity between the PLC and the remote control station.

These steps help restore proper communication and resolve the error.