A046 - Clamping Device Has Closed Prior To Feed Out Complete - LNS QUICK LOAD SERVO S3 Troubleshooting And Spare Parts Manual

Hide thumbs Also See for QUICK LOAD SERVO S3:
Table of Contents

Advertisement

Chapter 1: Alarms
A046 – Clamping Device Has Closed Prior to Feed Out Complete
CLAMPING DEVICE HAS
CLOSED PRIOR TO
COMPLETING THE
FEED OUT
POSSIBLE CAUSES:
-LATHE PROGRAMMING
ERROR
-CLAMPING SIGNAL
FAULTY (PLC INPUT
A1)
Description:
The Clamping Device Has Closed Prior To Completing The Feed Out alarm occurs if the input for the clamping device closed is
detected before the value of the Input Part Length parameter is reached.
Solution:
Verify that the clamping device is closing properly and that the Clamping Signal Active interface parameter is set in conjunction with
how the interface signal is being sent.
A046
1 - 1 5
QUICK LOAD SERVO S3

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the QUICK LOAD SERVO S3 and is the answer not in the manual?

Questions and answers

tom,
March 18, 2025

LNS BARFEEDER sps no response , how do i fix this error

1 comments:
Mr. Anderson
March 18, 2025

The SPS No Response alarm on the QUICK LOAD SERVO S3 occurs due to a communication problem between the remote control station and the LNS PLC. To fix this error:

1. Check the connectors between the PLC and the remote control station inside the cross piece to ensure they are correctly attached.
2. Verify continuity between the PLC and the remote control station.

These steps help restore proper communication and resolve the error.