Setpoint channel and closed-loop control
7.4 Vector speed/torque control with/without an encoder
7.4.8

Current controller adaptation

Current controller adaptation can be used to adapt the P gain of the current controller and
the dynamic precontrol of the I
The current controller adaptation is directly activated with setting p1402.2 = 1 or deactivated
with p1402.2 = 0.
Using p1959.5, it is automatically activated (p1959.5 = 1) or deactivated (p1959.5 = 0).
Figure 7-23
When swapping the I
adaptation appears as follows:
Figure 7-24
Function diagram
FP 6714
Parameters
• p0391
• p0392
• p0393
• p1402
• p1703
• p1715
• p1717
• p1959
486
current controller depending on the current.
q
Current controller adaptation for p0393 < 1, with p0391 < p0392
interpolation points (e.g. for induction motors), the current controller
q
Current controller adaptation with swapped I
p0392 < p0391
Vector control - Iq and Id controller
Current controller adaptation, starting point KP
Current controller adaptation, starting point KP adapted
Current controller adaptation P gain scaling
Current control and motor model configuration
Isq current controller precontrol scaling
Current controller P gain
Current controller integral time
Rotating measurement configuration
interpolation points for p0393 > 1, with
q
Operating Instructions, 12/2018, A5E36652151A
Enclosed Drives