9.5.3

Blocking protection

Description
The "Motor blocked" fault is only triggered when the speed of the drive is below the
adjustable speed threshold in p2175.
● For vector control, then the speed controller must also be at its limit.
● For V/f control, then the current limit must also be reached.
Once the on delay (p2177) has elapsed, the message "Motor blocked" and fault F07900 are
generated.
The blocking monitoring enable can be deactivated via p2144.
Figure 9-50
Blocking protection
Enclosed Drives
Operating Instructions, 12/2018, A5E36652151A
CO: Power unit overload I
CO: Power unit temperatures
Power unit overload response
CO: Power unit alarm threshold model temperature
Power unit alarm I
t overload
2
Fault thermal overload power unit
Alarm, thermal overload power unit
Functions, monitoring and protective functions
9.5 Monitoring functions and protective functions
t
2
699