Changing analog output 0 from current to voltage output –10 V ... +10 V (example)
Changing the analog output 0 from current to voltage output –10 ... +10 V (example) and setting the
characteristic
Enclosed Drives
Operating Instructions, 12/2018, A5E36652151A
Voltage output present at terminal 1, ground is at terminal 2
Set analog output type 0 to -10 ... +10 V.
Voltage output present at terminal 1, ground is at terminal 2
Set TM31.AO_type [analog output 0] to -10 ... +10 V.
Set TM31.AO_char. x1 to 0.00%.
Set TM31.AO_char. y1 to 0.000 V.
Set TM31.AO_char. x2 to 100.00%.
Set TM31.AO_char. y2 to 10.000 V.
Output terminals
8.2 Analog outputs