Fire as a result of inadequate installation
When installation is inadequate (failure to observe the cooling clearances or insufficient
distances from combustible objects), there is a risk of fire leading to death or serious injury.
• Maintain a cooling clearance of 7.9 inches (200 mm) on all sides of the braking resistor
• Maintain a sufficient distance from combustible objects.
Burns caused by hot braking resistor surfaces
During operation, the braking resistor can reach high temperatures and can cause burns if
touched.
• Allow the braking resistor to cool down before starting any work.
• Use the appropriate personnel protection equipment, e.g. gloves.
Table 4- 40
Width
Height
Depth
Figure 4-23
Dimension drawing of braking resistor rated 25 kW - Specifications in inches (mm)
Enclosed Drives
Operating Instructions, 12/2018, A5E36652151A
WARNING
with ventilation grills.
CAUTION
Dimensions of the braking resistors
Unit
inch (mm)
inch (mm)
inch (mm)
25 kW resistor (option L61/L64)
29.1 (740)
23.8 (605)
19.1 (485)
Electrical installation
4.9 Additional connections
50 kW resistor (option L62 / L65)
31.9 (810)
52.1 (1325)
19.1 (485)
133