Table 6- 56
Assigning the Modbus register to the parameters - process data
Register Description
Control data
40100
Control word (see List Manual,
function diagram 2442)
40101
Main setpoint
40102
STW 3
40103
STW 4
40104
PZD 5
40105
PZD 6
40106
PZD 7
40107
PZD 8
40108
PZD 9
40109
PZD 10
Status data
40110
Status word (see List Manual,
function diagram 2452)
40111
Main actual value
40112
ZSW 3
40113
ZSW 4
40114
PZD 5
40115
PZD 6
40116
PZD 7
40117
PZD 8
40118
PZD 9
40119
PZD 10
Table 6- 57
Assigning the Modbus register to the parameters - parameter data
Register Description
Drive identification
40300
Actual power unit code number
40301
Control Unit firmware
Drive data
40320
Rated power of the power unit
40321
Current limit
40322
Ramp-up time
40323
Ramp-down time
40324
Reference speed
Enclosed Drives
Operating Instructions, 12/2018, A5E36652151A
Access
Unit
Scaling
R/W
-
1
R/W
-
1
R/W
-
1
R/W
-
1
R/W
-
1
R/W
-
1
R/W
-
1
R/W
-
1
R/W
-
1
R/W
-
1
R
-
1
R
-
1
R
-
1
R
-
1
R
-
1
R
-
1
R
-
1
R
-
1
R
-
1
R
-
1
Ac-
Unit
Scaling
cess
R
-
1
R
-
1
R
kW
100
R/W
%
10
R/W
s
100
R/W
s
100
R/W
RPM
1
6.12 Communication via MODBUS TCP
ON/OFF text or
Data / parameter
value range
-
Process data 1
-
Process data 2
-
Process data 3
-
Process data 4
-
Process data 5
-
Process data 6
-
Process data 7
-
Process data 8
-
Process data 9
-
Process data 10
-
Process data 1
-
Process data 2
-
Process data 3
-
Process data 4
-
Process data 5
-
Process data 6
-
Process data 7
-
Process data 8
-
Process data 9
-
Process data 10
ON/OFF text or
Data / parameter
value range
0 ... 65535
0 ... 65535
0 ... 655.35
0.0 ... 6553.5
10.00 ... 655.35
10.00 ... 655.35
6 ... 65535

Operation

r0200
r0018 / 10000
r0206
p0640
p1120
p1121
p2000
421