Siemens SINAMICS S150 NEMA Operating Instructions Manual page 259

Converter cabinet units
Hide thumbs Also See for SINAMICS S150 NEMA:
Table of Contents

Advertisement

Note
Enter the motor-side filter
A filter on the motor side must be entered in p0230:
• Option L08 – motor reactor: p0230 = 1
• Option L10 – dv/dt filter plus Voltage Peak Limiter: p0230 = 2
When p0230 = 4 "External sine-wave filter", a separate sine-wave filter can be entered.
An input mask for specific filter data then appears.
NOTICE
Damage to the dv/dt filter if it is not activated during commissioning
The dv/dt filter may be damaged if it is not activated during commissioning.
• Activate the dv/dt filter during commissioning.
Note
Motor reactor
If a motor reactor (option L08) is being used, the option selection must be activated,
otherwise the closed-loop motor control will not be able to operate in an optimum fashion.
Note
Do not use a selection
The choice "no selection" is also available as default setting for the command and setpoint
sources; if selected, no default settings are applied for the command and setpoint sources.
Enclosed Drives
Operating Instructions, 12/2018, A5E36652151A
5.5 Initial commissioning with the AOP30
Final confirmation
Confirm the basic parameters to save
them.
Once you have selected "Continue" and
activated your entries with <F5>, the basic
parameters you entered are permanently
saved and the calculations required for
closed-loop control are carried out.
Commissioning
257